Quick Find
Energy Experts
- All users
- Laurence Jones
- Adrian Wright
- Linn Rafferty
- Ross Lammas
- Simon Forsyth
- Tim Pullen
- Howard Johns
- Hugo House
- John Martin
- Matthew Rhodes
- Pete Roberts
- Chris Davis
- John Barker-Brown
- John Lightfoot
- Barry Nutley
- Chris Rudge
- Gabriel Wondrausch
- Paul Hutchens
- David Hunt
- Graham Eastwick
Other Contributors
Cathy Debenham Gilly JonesGuest Bloggers
Aldous EverardAlister ScottChris RowlandDavid FieldsDuncan McIntoshGordon TraillHarvey JonesJames PageJon EdgeLisa HallMatt CodyMax SillarsMerlin HymanMike MackmurdieNick RoachRob PalgraveRoger CroftSimon FixterStewart BoyleArchive
Posting rulesRecent Comments
- Informative commercial website here concerning low energy LED downlighters.…
comment by andytee
- A very interesting post. It is up to everyone in the industry to put out a …
comment by ekland-ltd-ex4-7bd
- A properly designed condensing tumble drier should use the heat from the he…
comment by nigeldodd
Tag Cloud
YouGen Blog
How to install a heat pump into an existing property
Posted by John Barker-Brown on 21 February 2011 at 9:18 am
As the advantages of heat pumps become better known and with the expected Renewable Heat Incentive, more people are looking at whether the technology can be applied to their existing properties.
The advantages of installing a heat pump in a new build property is well documented. It is also possible to install heat pumps into existing properties, but there are various considerations which which determine how well, and even if, a heat pump will work effectively.
1. Sizing: the heat loss of the property is determined by how well the building is insulated. If the insulation is not known then it becomes difficult to size the heat pump accurately. The only way this can be achieved with any degree of accuracy is to commission a Standard Assessment Procedure report (SAP) which takes into account the build, insulation, heating system, etc and can be used to determine a peak heat load.
2. Insulation: This plays a big part in how effectively a heat pump operates. As the heat pump produces a lower flow temperature than traditional fossil fuel systems, the amount of heat it transfers to a room is limited (for a given heat emitter area) and is less than the traditional boiler.
If you raise the heat pump outlet temperature to its maximum (approx 50 degrees C) the heat pump has to work harder and its efficiency decreases. The coefficient of performance (CoP) at 50C is now only 3 as opposed to 4 (at 35C).
You also need to think about whether the actual heat emitting device, i.e. radiators, underfloor, etc, will output enough heat at the heat pump’s lower flow temperatures, to keep the building warm enough to be comfortable, particularly when the temperature outside is cold.
Reducing the energy requirement for any building should be a central theme to the design process. Any investment in an upgraded insulation specification will have a far swifter payback than the return on any renewable technology. For this reason, you should consider improving the insulation level beyond the minimum requirements stipulated in the Building Regulations.
If your building is very poorly insulated, the low temperature output from the heat pump may mean that it will never get warm and that the running costs for the heat pump are expensive. Possibly even higher than the existing fuel choice, particular if it is mains gas. We do not recommend installing a heat pump in a poorly insulated building.
3. The existing heating system: many existing properties will be heated by radiators. As radiators have a smaller surface area than underfloor heating, they need a higher flow temperature to provide heat. Before a radiator will provide any heat the flow temperature needs to be at least 45oC. This means that the efficiency of the heat pump is reduced and the Coefficient of Performance (CoP) drops from 4 (for underfloor heating in screed) to 3. This is a drop in efficiency of approximately 25% (and will result in higher electricity bills).
Due to the lower flow temperatures produced by a heat pump compared to a traditional fossil fuel boiler, the surface area of the radiator may need to be increased to provide the required heat into the building. Therefore all radiators will need to be oversized.
However, there are a number of situations which suit a radiator system, such as Social Housing schemes and clients may well accept the lower efficiencies of a radiator system for the ease of installation benefits, quicker response than underfloor heating, etc.
4. Land Available: This criteria only applies for ground source heat pumps, which uses renewable stored solar energy from the ground to heat the property; it absorbs this energy by means of a ground array buried within the property’s boundaries.
It is important to make sure that the correct amount of pipe for the application is buried and that it is buried correctly. If not enough pipe is installed then the ground could potentially run out of energy mid heating season, leaving you cold and without heat.
It is important to remember that if the heat pump is producing domestic hot water as well as space heating, more ground array is needed, as there is an additional all year round load on the ground. As a guide roughly 2 to 2.5 times the area being heated is required to install horizontal ground arrays.
If you don't have enough land available an alternative to horizontally laid ground arrays is a vertical drilled borehole. These can be down to a depth of over 100m. Drilling a borehole is a specialist activity and as such can be expensive. As a guide these costs can be £40-£45 per m.Any existing building where a heat pump is proposed needs to be looked at very carefully as a heat pump is not always the correct choice.
Photo: Kensa
About the author: John Barker-Brown is special projects manager at British heat pump manufacturer Kensa Engineering.
If you have a question about anything in the above blog, please ask it in the comments section below.
Comments
4 comments - read them below or add one
Dear MrsN,
Thanks for the comments. I'm glad you find the blogs useful.
With any heat pump, insulation is the key and we would always recommend that the maximum amount of insulation is fitted. Without insulation the heat pump has to operate at a higher temperature and becomes less renewable as it uses more electricity. In the worse case you could end up with high energy bills and cold rooms. For any heat pump insulation we would recommend levels of insulation to at least current Building Regs.
If you are considering an air source make sure that the unit will provide the correct output at the higher internal temperature and low ambient temperature outside. A number of manufacturers state the outputs at 35C internal and 7C external. Deviation from these conditions will decrease the output of the unit.
You will also need planning permission for the air source and take into consideration defrost cycles, which either use direct immersion or take heat out of the building (from a buffer vessel).
With regards to running oil upstairs and a heat pump downstairs, it is possible to do this, however you need to ensure that the heating systems are completely separate (otherwise with its high return temperature the oil boiler will take all the load, and the heat pump will never turn on) and both heating systems are operated at the same time. If they aren't then the air source needs to be sized for the whole property as it will try and heat the whole building.
Finally with regards to the underfloor and running this first on oil, just make sure that the underfloor is designed for a heat pump. This generally means closer centres on the pipes due to the lower flow temperature from the heat pump. You might also need to close any mixing valves on the system as for a heat pump these are not required but are generally fitted for an oil boiler.
John Lightfoot who also writes on this website is a good contact for air source. My company Kensa only manufacture ground source as we feel this is a better solution.
Hi John,
Can I ask some really basic questions? I have read the blogs here which are very helpful & so far so good. We have just had an offer accepted on a mid-1800s cottage needing complete renovation which currently runs oil fired CH/HW & I am desperate to reduce our dependence on this. There is also a damp problem as the floors consist of bricks & then earth so we have been advised to dig out put in concrete screed/insulation etc. So, the obvious answer seems to be underfloor heating throughout ground floor with an air source heat pump. Upstairs and HW would still run on oil. QUESTIONS:
Does this sound all sound logical & feasible to you?
In terms of the 'sufficient insulation' required would good loft insulation, secondary glazing & brick walls be likely to be sufficient?
Lastly, as we probably can't afford to do all the work/secondary glazing in one go, have you ever heard of underfloor heating being fitted & running off oil initially then an air source heat pump being retro-fitted to the system a year later once all the insulation was in place?
Thanks for your advice & sorry for long-winded questions!
MrsN
Kensa Engineering LtdComment left on: 23 June 2011 at 2:50 pm
Hi Bob,
Thanks for the comment. Its interesting to see that you have found what we have always thought written in a book! Our general stance with clients now is for existing installs either to
a) if they haven't yet installed, reduce their boiler temperature to around 50C and see if the radiators provide enough heat.
b) if they have committed to a heat pump, leave the existing radiators and only replace if the room feels cold.
c) have a radiator survey done.
A number of our clients are finding that they are warm enough on their existing radiators, simply due to the original heating engineer oversizing them.
Bob IrvingComment left on: 23 June 2011 at 10:06 am
In my research into heat pumps, I found a comment in one of the older books "Heat pump" by McMullan - there are hardly any new ones! - that radiators are likely to be oversized on existing systems. I quote
"Boilers are cheap, and it is customary to install quite large boilers in quite small buildings, to ensure that there will always be enough heat. As an example, a house of 100 m2, which in typical cold winter weather might require 5-7 kW of heating, might easily be fitted with a boiler of 18 kW ... output. This means that enough radiator area has to be provided to emit 18 kW at reasonable water temperatures. ... Consequently it is necessary to install radiators with enough area to dissipate only about 7 kW at 50/60°C, which by a happy chance is almost exactly 40% of 18 kW." (McMullen, 1981, p107)
This implies that (probably older) radiators already installed in houses would be sufficiently large enough to provide enough output from a hp at 45-55 degrees. Does anyone have any experience of this?
Leave a comment
You must log in to make a comment. If you haven't already registered, please sign up as a company or an individual, then come back and have your say.
Follow us on Twitter
Solar PV remains one of the best investments around say trade bodies http://t.co/dxKDhVXh yesterday
@Kristian_Marr I'm intrigued to know what's involved in being a DECC youth panellist yesterday
@PassivSystemsHQ Will Smart Meters put consumers in the driving street? Or will the big six still have the upper hand? #cleanrevolution yesterday




John Barker-Brown from Kensa Engineering LtdComment left on: 13 July 2011 at 10:39 am